Читать книгу Gas Insulated Substations - Группа авторов - Страница 35

1.2.14 Design Pressure of Enclosures

Оглавление

Relative pressure used to determine the design of the enclosure. It is at least equal to the maximum pressure in the enclosure at the highest temperature that the gas used for insulation can reach under specified maximum service conditions. The transient pressure occurring during and after a breaking operation (e.g., a circuit breaker) is not to be considered in the determination of the design pressure, as defined in IEC 62271‐203.