Читать книгу Smart Grids and Micro-Grids - Umashankar Subramaniam - Страница 47

2.5.2.3 Typical Case Study in MATLAB-Simulink

Оглавление

A MATLAB-Simulink model of the three-phase inverter system shown in Figure 2.7 is developed with the specification listed in Table 2.4. The filter parameter are selected based using following equations [16, 17]

(2.33)

(2.34)

Table 2.4 Specifications of battery-converter system for AC microgrid.

Parameter Value
Nominal voltage (VB) 700 V
Rated capacity 150 Ah
Initial SOC 60%
inverter side inductance (L) and ESR (rL) of inductor 1mH, 0.005Ω
Filter capacitor (Cf) 20 µF
AC load PL=1000 W QL =100 VAR
AC microgrid voltage (Vphase(rms)) grid side inductance Lg 220 V300 µH

(2.35)

Where P is the rated output active power of one phase for three-phase full-bridge inverter, Vg is the phase voltage, Vdc is the dc link voltage fsw is switching frequency, Ka = 0.2,

The control is implemented in the Simulink platform. The commands “Modecommand” along with the power to be exchanged (Pref, Qref), with microgird are sent to the controller from the EMS of the microgrid. The feedback signals PCC voltage (Vsx), inverter current (iLx), grid voltage (Vgx) are also input to the controller.

Figure 2.9 shows the results for the case when Modecommand = 1, i.e. battery converter system is in grid-connected mode. Initially, the battery was having SOC=60% and Qref was set to 0 value. Pref was set to 10kW, which was changed to 5kW at t=3.5 sec. At t=2.5 sec, Qref was set to 1kVAr, subsequently changed to zero value at t=5 sec. At t=7 sec, Pref was set to -1kW so that the power can be drawn from the grid to charge the battery. From the waveform, it is evident that the controller could track the reference power as stated by the EMS of the microgrid. Also, during the time up to 7 sec, the battery SOC and battery voltage were decreasing as ESS was discharging to supply the power to the grid.

To show that the controller would work for the case when the battery converter system is in islanded mode, i.e., Modecommand = 0 is received from the EMS, the battery converter system is made to maintain the PCC voltage. Initially, the system was operated in grid-connected mode and was supplying 10k W of real power to the grid. At t=1 sec, the grid was disconnected and reference voltage to be maintained at PCC is given to the controller. At 1.5 sec, the battery converter system is again connected back to the grid. Figure 2.10 shows the result for this case. From the waveforms, it is clear that the converter was able to maintain the PCC voltage even for the case when the grid was disconnected and again connected back to the grid.


Figure 2.9 Performance of the controller when the battery converter system is in grid connected mode.


Figure 2.10 Waveform of PCC voltage, real and reactive power exchanged fed for the condition when the battery converter system switches between grid-connected mode and islanded mode.

Smart Grids and Micro-Grids

Подняться наверх