2.7.12.3 Conclusion

Оглавление

This motor operating with the proposed cable 3c #1/0 AWG is acceptable for the actual cable length of 100 m. If the distance is doubled to 200 m, a new heavier cable would have to be selected as the ΔV = 16.4% > 15% is over the operating limit.