1.7.6 Machine Losses [4]

Оглавление

Current flows through the machines conductors generating heat (a loss). However, there are a number of other sources within a working synchronous generator that produce heat and, thus, losses. The following is a list of some of those sources of losses:

 I2R losses of stator winding

 I2R losses of rotor winding

 Core loss

 Stray load loss

 Excitation system lossFigure 1.7-8 Steady‐state equivalent circuit and vector diagram. (a) Generator operation and (b) motor operation.

 Windage and Friction loss

 Ventilation and cooling loss

In determining I2R losses, the resistance of windings should be corrected to the reference temperature. During the commissioning tests for a generator, the OEM may use a common reference temperature of 75 °C. When calculating the actual losses at a specific temperature, then the resistance at 75 °C must be converted to the resistance at the desired temperature.