Читать книгу Explosion Vented Equipment System Protection Guide - Robert C. Comer - Страница 14

Оглавление

Typical Dust Collection System Checklist

Example (Rectangular Dust Collector)

System Identification: Typical dust collector example

Process Product: No specific product assumed

Product Pmax_____________ Product Kst________ Pred = 5.0 psi assumed

Basis of Pmax and Kst: Was product dust tested ____Y ____X __N

Were values approximated from a chart ____Y ___X ___N

Other: Average values assumed for this example

Dust collector: If square or rectangular

 Pressure rating from manufacturer: ±20 in water gauge

 Basis for rating: 60% of 0.2% yield strength, or other__________

 Is vessel located inside or outside? Inside

 Top width: 97.75 in. Depth: 38.25 in. Height: 27.75 in.

 Top sheet thickness: 10 ga. (0.1345 in.)

 Sides height: 108.25 in.

 Sidewall thickness: 10 ga. (0.1345 in.)

 Reinforcing on top or walls: None

 Volume of dust collector: N/A

Dust collector: If cylindrical

 Pressure rating from manufacturer:_________________

 Basis for rating: ________% of 0.2% yield strength, or other_______

 Diameter: _________

 Type of top: Flat______ Ellipsoidal__________ Torispherical_______

 Thickness of top: _______

 Thickness of cylinder wall: _______

 Length of cylinder: ______________

 Volume of dust collector: ______________________________________

 Hopper height: 30.50 in. Discharge size: 9.25 in. × 9.25 in.

 Hopper wall thickness: 10 ga. (0.1345 in.)

 Dust collector/hopper flange size and thickness: 2″ × 2″ × 1/4″ angle

 Bolt size and spacing: _________________________________________

 Volume of hopper: N/A

 Number of bags/cartridges: N/A

 Bag/cartridge diameter: __________ Number of bags/cartridges: ______

 Bag/cartridge volume: ______________

 Access door width and height: 37.875 in. × 40 in.

 Access door thickness: 10 ga. (0.1345 in.)

 Reinforcing on door: None

 Type of latching:Clamps________________ Bolts _________________________Hinges ____________ Hinge pin diameter __________________

 Nozzles: Diameter __________________________________

 Dusty air inlet dimensions: _____________________________

 Clean air outlet dimensions: ____________________________

 Leg supports:Size: ______ Number of supports: 4 Length of supports: 78.50 in.Footpad size and thickness: 7.50 in. × 7.50 in. × 1/2 in.Attachment to floor or ground: 3/4 in bolts to floor

Explosion vent information:

 Manufacturer/part number: N/A

 Size: Round _______ Square/rectangular: 24 in. × 24 in.

 Vent pressure rating: 1.0 psi ± 0.25 psi Vent area: ___________________

 Flange size: 2″ × 2″ × 1/4″ angle Bolt size and number

 Distance from top of dust collector: 35 in.

Duct information:

 Size: 24 in. × 24 in. Length: Wall thickness: 10 ga. (0.1345 in)

 Any bends at end of duct?

Screw conveyor:

 Cover width __________ Cover length _________ Thickness _________

 Spacing and size of bolts or clamps on cover:

Explosion Vented Equipment System Protection Guide