Читать книгу Practical Power Plant Engineering - Zark Bedalov - Страница 63
2.7.6 13.8 or 33 kV Switchgear for a Larger Plant
ОглавлениеThere is a correlation between the rating of the switchgear incoming breakers and the incoming transformers ratings.
For an even larger plant primary distribution system, the use of 33 kV would be likely, with the transformer incoming and bus tie breakers rated at 2000 A. These 33 kV breakers can accommodate 60/80 MVA, ONAN/ONAF incoming transformers at 80% of their breaker nameplate ratings. The switchgear bus can also be selected as 2000 A, while the plant feeders to the individual plant load centers will be any of those available: 1200, 1600, or 2000 A breakers. In this instance, we can standardize on a continuous rating of 1200 A, which can be loaded up to 960 A (55 MVA at 33 kV), i.e. 80% of the breaker nominal rating and 100% of the breaker nameplate rating for a temporary emergency usage.
Here is the switchgear for a large plant either at 13.8 or 33 kV, metal‐clad or 33 kV gas insulated switchgear (GIS) with vertical sections having single breaker positions. In summary, the two switchgear assemblies are rated as follows:
Nominal voltage | 13.8 kV | 33 kV |
BIL, indoors/outdoors | 95 kV/110 kV | 170 kV |
Phasing | 3 ph, 3 w | 3 ph, 3 w |
Interrupting capacity | 40 kA r.m.s. symmetrical | 31 kA r.m.s. symmetrical |
Construction | Metal‐clad | Metal‐clad or GIS |
Incoming and tie breakers | 2000 A | 2000 A |
Normal operation, incomers | 37.6 MVA at 80% | 72 MVA at 80% rating |
Maximum loading, incomers | 47 MVA at 100% | 92 MVA at 100% rating |
Feeder breakers | 1200 A | 800, 1200 A |
The breaker 2000 A rating for the incoming and tie breakers at the 13.8 kV switchgear is more than adequate for both normal and emergency duty. The branch feeders on the switchgear are usually positioned in such a way to minimize the power flow across the bus tie breaker.
Evidently, 13.8 kV voltage can be used for the plants up to 50 MVA. Certainly, 20 or 33 kV voltage can be equally applied and used for this 40 MVA plant as well as in even larger industrial facilities as the primary plant distribution voltage. The economies of these options would have to be worked out during the design phase of the project, when the largest plant loads are confirmed.