Читать книгу Practical Power Plant Engineering - Zark Bedalov - Страница 24
1.2.8 Generated Cable List
ОглавлениеTable 1.1 Load list (simplified).
ID | Name | Volt | kW | MCC | In service | Type |
40 PU 003 | Feed Pump, Water Tank 1 | 460 | 15 | MCC11 | 1 | T1 |
40 PU 004 | Feed Pump, Water Tank 1 | 460 | 15 | MCC11 | SB | T1 |
30 AG 006 | Agitator, Tank 6 | 460 | 10 | MCC03 | 1 | T1 |
30 CR 001 | Crane, 60 Tone, Main Hall | 460 | 100 | MCC03 | 1 | F1 |
10 RF 003 | Crusher Roof Fan | 460 | 1 | MCC 01 | 1 | T3 |
In service: 1 = operating, SB = on standby.
Type: this is the designation of the type of operating circuit to be implemented.
Table 1.2 Cable list (simplified).
Cable ID | Cable size | kW | Type/class | From | To | Length |
40 PU 003 P | 1‐3/c #10 AWG, | 20 | Teck 600V | MCC11 | PU Motor | 120 |
40 PU 003 C1 | 1‐5/c #16 AWG, | Teck 300V | MCC11 | PLC 2 | 15 | |
40 PU 003 C2 | 1‐3/c #14 AWG, | Teck 300V | MCC11 | PB Stn | 120 | |
40 PU 004 P | 1‐3/c #10AWG, | 20 | Teck 600V | MCC11 | PU Motor | 120 |
40 PU 004 C1 | 1‐5/c #16 AWG, | Teck 300V | MCC11 | PLC 2 | 15 | |
40 PU 004 C2 | 1‐3/c #14 AWG, | Teck 300V | MCC11 | PBStn | 120 | |
40 PU 004 C3 | 1‐2/c #14 AWG, | Teck 300V | MCC11 | TH1 | 130 | |
30 AG 005 P | 1‐3/c #12AWG, | 15 | Teck 600V | MCC05 | PU Motor | 85 |
30 AG 005 C1 | 1‐5/c #16 AWG, | Teck 300V | MCC05 | PLC 3 | 20 | |
30 AG 005 C2 | 1‐3/c #14 AWG, | Teck 300V | MCC05 | PB Stn | 85 | |
10 SP 003 P | 1‐3/c # 12 AWG, | 5 | Teck 600V | MCC01 | PU Motor | 60 |
10 SP 003 C2 | 1‐3/c #14 AWG, | Teck 300V | MCC01 | PB Stn | 60 |